modelEnable_TOut_hOut

Model validates economizer disable in case outdoor air conditions are above cutoff

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.Enable for the following control signals: TOut, TOutCut, hOut, hOutCut.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTOutCutOutdoor air temperature cutoff
Buildings.Controls.OBC.CDL.Reals.Sources.ConstanthOutCut1Outdoor air enthalpy cutoff
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.EnableenaDisMulti zone VAV AHU economizer enable disable sequence
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.EnableenaDis1Multi zone VAV AHU economizer enable disable sequence
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Subsequences.EnableenaDis2Multi zone VAV AHU economizer enable disable sequence
Buildings.Controls.OBC.CDL.Reals.Sources.SinTOutOutdoor air temperature
Buildings.Controls.OBC.CDL.Reals.Sources.SinhOutOutdoor air enthalpy

Revisions

  • June 13, 2017, by Milica Grahovac:
    First implementation.