modelController_Disable
Validation model for disabling the multi zone VAV AHU economizer modulation and damper position limit control loops
Information
This example validates
Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Controller
for control signals which disable modulation control loop only (eco block)
and both minimum outdoor airflow and modulation control loops (eco1 block).
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Controller | eco | Multi zone VAV AHU economizer | |
| Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.Economizers.Controller | eco1 | Multi zone VAV AHU economizer |
Revisions
-
February 5, 2022, by Jianjun Hu:
First implementation.