packageASHRAE62_1
Package of sequences specifying outdoor airflow setpoint by complying with ASHRAE 62.1
Information
This package contains sequences to set the minimum outdoor airflow setpoint for compliance with the ventilation rate procedure of ASHRAE 62.1. It is implemented according to Section 5.16.3.1 of ASHRAE Guideline G36, May 2020.
- Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.ASHRAE62_1.AHU conducts AHU level calculations for specifying minimum outdoor airflow rate,
- and Buildings.Controls.OBC.ASHRAE.G36.AHUs.MultiZone.VAV.SetPoints.OutdoorAirFlow.ASHRAE62_1.SumZone finds the sums and the maximum of outputs from zone level calculations. They become inputs of AHU level calculation.
Contents
| Name | Description |
|---|---|
| Outdoor airflow related calculations at the AHU level | |
| Calculate the sum of zone level setpoints | |
| Collection of validation models |
Revisions
-
March 13, 2022, by Jianjun Hu:
First implementation.