blockSupplyAirTemperature

Validation model for supply air temperature setpoint subsequence

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.FanCoilUnits.Subsequences.SupplyAirTemperature. Each of the four instances of the controller represents operation with different inputs for heating and cooling loop signals, and different configuration parameters of fan coil unit with presence or absence of heating and cooling coils, as described in the instance comments.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.ASHRAE.G36.FanCoilUnits.Subsequences.SupplyAirTemperatureTSupAirInstance demonstrating heating signal operation
Buildings.Controls.OBC.ASHRAE.G36.FanCoilUnits.Subsequences.SupplyAirTemperatureTSupAir3Instance demonstrating cooling signal operation when heating coil is absent
Buildings.Controls.OBC.ASHRAE.G36.FanCoilUnits.Subsequences.SupplyAirTemperatureTSupAir2Instance demonstrating heating signal operation when cooling coil is absent
Buildings.Controls.OBC.ASHRAE.G36.FanCoilUnits.Subsequences.SupplyAirTemperatureTSupAir1Instance demonstrating cooling signal operation
Buildings.Controls.OBC.CDL.Reals.Sources.SinsinSupply air temperature signal
Buildings.Controls.OBC.CDL.Reals.Sources.Sinsin3Supply air temperature signal
Buildings.Controls.OBC.CDL.Reals.Sources.Sinsin5Cooling loop signal
Buildings.Controls.OBC.CDL.Reals.Sources.Sinsin6Supply air temperature signal
Buildings.Controls.OBC.CDL.Reals.Sources.Sinsin8Heating loop signal
Buildings.Controls.OBC.CDL.Reals.Sources.Sinsin4Supply air temperature signal
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantconZone heating temperature setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.Constantcon1Zone cooling temperature setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.Constantcon2Zone heating temperature setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.Constantcon3Zone cooling temperature setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.Constantcon4Zone heating temperature setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.Constantcon6Zone cooling temperature setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.Constantcon5Heating loop signal
Buildings.Controls.OBC.CDL.Reals.Sources.Constantcon7Heating loop signal
Buildings.Controls.OBC.CDL.Reals.Sources.Constantcon8Cooling loop signal
Buildings.Controls.OBC.CDL.Reals.Sources.Constantcon9Cooling loop signal
Buildings.Controls.OBC.CDL.Logical.Sources.Constantcon10Boolean fale signal

Revisions

  • March 18, 2022, by Karthik Devaprasad:
    First implementation.