modelTuning_uEcoSta_uTowFanSpeMax
Validate water side economizer tuning parameter sequence
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Tuning.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Tuning | wseTun | Tests tuning parameter increase due to a dip in tower fan speed | |
| Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Tuning | wseTun1 | Tests tuning parameter remains constant inspite of a dip in tower fan speed due to the prolonged WSE on status | |
| Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Tuning | wseTun2 | Tests tuning parameter decrease due to WSE being on for a long time before disable | |
| Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Tuning | wseTun3 | Tests tuning parameter remains constant despite of a dip in tower fan speed due to the prolonged WSE on status | |
| Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Tuning | wseTun4 | Tests anti-windup |
Revisions
-
October 15, 2018, by Milica Grahovac:
First implementation.