modelTuning_uEcoSta_uTowFanSpeMax

Validate water side economizer tuning parameter sequence

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.Tuning.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.TuningwseTunTests tuning parameter increase due to a dip in tower fan speed
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.TuningwseTun1Tests tuning parameter remains constant inspite of a dip in tower fan speed due to the prolonged WSE on status
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.TuningwseTun2Tests tuning parameter decrease due to WSE being on for a long time before disable
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.TuningwseTun3Tests tuning parameter remains constant despite of a dip in tower fan speed due to the prolonged WSE on status
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Economizers.Subsequences.TuningwseTun4Tests anti-windup

Revisions

  • October 15, 2018, by Milica Grahovac:
    First implementation.