packageValidation
Collection of validation models
Information
This package contains validation models for the classes in Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Pumps.ChilledWater.Subsequences.
Note that most validation models contain simple input data which may not be realistic, but for which the correct output can be obtained through an analytic solution. The examples plot various outputs, which have been verified against these solutions. These model outputs are stored as reference data and used for continuous validation whenever models in the library change.
Contents
| Name | Description |
|---|---|
| Validate sequence for enabling lag pump for primary-only plants using differential pressure pump speed control | |
| Validate sequence for enabling lead pump of plants with dedicated primary chilled water pumps | |
| Validate sequence for enabling lead pump of plants with headered primary chilled water pumps | |
| Validate sequence of calculating local differential pressure setpoint | |
| Validate sequence of controlling chilled water pump speed for primary-only plants with local DP sensor hardwired to the plant controller | |
| Validate sequence of controlling chilled water pump speed for primary-only plants with remote DP sensor hardwired to the plant controller |