modelEnableLead_headered
Validate sequence for enabling lead pump of plants with headered condenser water pumps
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Pumps.CondenserWater.Subsequences.EnableLead_headered.
It shows the process of enabling and disabling the lead condenser water pump of the plants with headered condenser water pumps.
The instance enaLeaConPum shows that the lead pump is enabled at 300
seconds when there is chiller condenser water isolation valve being enabled. The pump
becomes disabled when both the chiller condenser water isolation valve and the waterside
economizer condenser water isolation valve are disabled.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Pumps.CondenserWater.Subsequences.EnableLead_headered | enaLeaConPum | Enable lead chilled water pump based on status of chilled water isolation valve status |
Revisions
-
August 4, 2019, by Jianjun Hu:
First implementation.