modelController

Validate condenser water pump control sequence

Information

This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Pumps.CondenserWater.Controller.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Pumps.CondenserWater.ControllerheaHavWseCondenser water pumps controller for plant with headered condenser water pump and have waterside economizer
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Pumps.CondenserWater.ControllerdedHavWseCondenser water pumps controller for plant with dedicated condenser water pump and have waterside economizer
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Pumps.CondenserWater.ControllerheaNoWseCondenser water pumps controller for plant with headered condenser water pump and without waterside economizer
Buildings.Controls.OBC.CDL.Reals.Sources.Rampramp1Block that generates ramp signal
Buildings.Controls.OBC.CDL.Reals.Roundround1Round real number to given digits
Buildings.Controls.OBC.CDL.Conversions.RealToIntegerchiStaConvert real to integer
Buildings.Controls.OBC.CDL.Integers.GreaterThresholdchiOnChiller status
Buildings.Controls.OBC.CDL.Logical.Sources.PulsewseStaWaterside economizer status
Buildings.Controls.OBC.CDL.Logical.Sources.ConstantfalLogical false
Buildings.Controls.OBC.CDL.Logical.Sources.PulsebooPulOutput boolean pulse
Buildings.Controls.OBC.CDL.Conversions.BooleanToIntegerbooToIntConvert boolean to integer
Buildings.Controls.OBC.CDL.Integers.AddaddIntAdd two integer inputs
Buildings.Controls.OBC.CDL.Logical.Sources.Constantcon1Constant false

Revisions

  • August 4, 2019, by Jianjun Hu:
    First implementation.