packageSetPoints

Sequences for setting the setpoints for chilled water control

Information

This package contains chilled water plant reset control sequences. The implementation is based on section 5.20.5.2. in ASHRAE Guideline 36-2021.

Contents

NameDescription
ChilledWaterPlantResetSequences to generate chilled water plant reset
ChilledWaterSupplySequences to generate setpoints of chilled water supply temperature and the differential pressure
ValidationCollection of validation models