modelController
Validation sequence of controlling tower fan speed
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Towers.FanSpeed.Controller.
It shows the calculations of the fan speed setpoint for the three different plants,
including the close coupled plants that have waterside economizer (cloCouWitWse),
the less coupled plants that have waterside economizer (lesCouWitWse),
and the close coupled plants that have no waterside economizer (cloCouNoWse).
-
For the close and less coupled plants with waterside economizer,
- if the plant is not enabled (before 600 seconds), the tower fan speed setpoint is 0.
-
if the economizer is enabled (600 seconds to 1320 seconds), the
fan speed setpoint equals to the
uTowSpeWSE. -
in the period when the chiller runs only (after 1320 seconds), the
speed setpoint is minimum of the
plrTowMaxSpeSet,uMaxTowSpeSetand the mapped setpoint.
-
For the close coupled plants without waterside economizer,
the setpoint calculation is same as the one with economizer
except there is no economizer enabled period. So when the chiller
is enabled, the setpoint equals to the
plrTowMaxSpeSet,uMaxTowSpeSetand the mapped setpoint.
Components
| Type | Name | Default | Description |
|---|---|---|---|
| Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Towers.FanSpeed.Controller | cloCouWitWse | Tower fan speed controller of plant that is close coupled and has waterside economizer | |
| Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Towers.FanSpeed.Controller | lesCouWitWse | Tower fan speed controller of plant that is less coupled and has waterside economizer | |
| Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Towers.FanSpeed.Controller | cloCouNoWse | Tower fan speed controller of plant that is close coupled and has no waterside economizer |
Revisions
-
September 15, 2019, by Jianjun Hu:
First implementation.