modelDampers

Validate model for controlling damper position of cooling only terminal unit

Information

This example validates BBuildings.Controls.OBC.ASHRAE.G36.TerminalUnits.CoolingOnly.Subsequences.Dampers for damper control of VAV cooling only terminal unit.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.ASHRAE.G36.TerminalUnits.CoolingOnly.Subsequences.Dampersdam1Output signal for controlling damper position
Buildings.Controls.OBC.CDL.Reals.Sources.RampuCooCooling control signal
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTZonZone temperature
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTSupAHU supply air temperature
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantVActMin_flowActive minimum airflow setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantVActCooMax_flowActive cooling maximum airflow setpoint
Buildings.Controls.OBC.CDL.Reals.Sources.SinVDis_flowDischarge airflow rate
Buildings.Controls.OBC.CDL.Reals.Sources.RampzonStaZone state
Buildings.Controls.OBC.CDL.Conversions.RealToIntegerreaToInt2Convert real to integer
Buildings.Controls.OBC.CDL.Reals.Roundround2Round real number to given digits
Buildings.Controls.OBC.CDL.Reals.Sources.RampoveFloOverride flow setpoint
Buildings.Controls.OBC.CDL.Conversions.RealToIntegerreaToInt1Convert real to integer
Buildings.Controls.OBC.CDL.Reals.Roundround1Round real number to given digits
Buildings.Controls.OBC.CDL.Reals.Sources.RampoveDamOverride damper position
Buildings.Controls.OBC.CDL.Conversions.RealToIntegerreaToInt3Convert real to integer
Buildings.Controls.OBC.CDL.Reals.Roundround3Round real number to given digits
Buildings.Controls.OBC.CDL.Logical.Sources.PulsebooPulAHU fan status

Revisions

  • February 10, 2022, by Jianjun Hu:
    First implementation.