blockActiveAirFlow

Output the active airflow setpoint for VAV reheat terminal unit

Information

This sequence sets the active cooling and heating maximum and minimum setpoints for VAV reheat terminal unit. The implementation is according to the Section 5.6.4 of ASHRAE Guideline 36, May 2020.

The setpoints shall vary depending on the mode of the zone group.

Setpoint OccupiedCooldown SetupWarm-upSetbackUnoccupied
Cooling maximum (VActCooMax_flow)VCooMax_flow VCooMax_flowVCooMax_flow 000
Cooling minimum (VActCooMin_flow)VOccMin_flow 00000
Minimum (VActMin_flow)VOccMin_flow0 0000
Heating minimum (VActHeaMin_flow)max(VHeaMin_flow,VOccMin_flow) VHeaMin_flow0VHeaMax_flowVHeaMax_flow 0
Heating maximum (VActHeaMax_flow)max(VHeaMax_flow,VOccMin_flow) VHeaMax_flow0VCooMax_flowVCooMax_flow 0

Parameters

TypeNameDefaultDescription
RealVCooMax_flowDesign zone cooling maximum airflow rate
RealVHeaMin_flowDesign zone heating minimum airflow rate, for the reheat box with water hot coil, it should be zero
RealVHeaMax_flowDesign zone heating maximum airflow rate

Connectors

TypeNameDefaultDescription
Buildings.Controls.OBC.CDL.Interfaces.IntegerInputuOpeModZone operation mode
Buildings.Controls.OBC.CDL.Interfaces.RealInputVOccMin_flowOccupied minimum airflow setpoint
Buildings.Controls.OBC.CDL.Interfaces.RealOutputVActCooMax_flowActive cooling maximum airflow setpoint
Buildings.Controls.OBC.CDL.Interfaces.RealOutputVActCooMin_flowActive cooling minimum airflow setpoint
Buildings.Controls.OBC.CDL.Interfaces.RealOutputVActMin_flowActive minimum airflow setpoint
Buildings.Controls.OBC.CDL.Interfaces.RealOutputVActHeaMin_flowActive heating minimum airflow setpoint
Buildings.Controls.OBC.CDL.Interfaces.RealOutputVActHeaMax_flowActive heating maximum airflow setpoint

Revisions

  • August 1, 2020, by Jianjun Hu:
    First implementation.