typeOutdoorAirSection
Enumeration to configure the outdoor air section
Information
Enumeration to define how minimum outdoor air and economizer function being designed in multizone AHU. Possible values are:
| Enumeration | Description |
|---|---|
DedicatedDampersAirflow |
Separate dampers for ventilation and economizer, with airflow measurement station. |
DedicatedDampersPressure |
Separate dampers for ventilation and economizer, with differential pressure sensor. |
SingleDamper |
Single damper for ventilation and economizer, with airflow measurement station. |
Literals
| Name | Description |
|---|---|
| DedicatedDampersAirflow | Separate dampers for ventilation and economizer, with airflow measurement station |
| DedicatedDampersPressure | Separate dampers for ventilation and economizer, with differential pressure sensor |
| SingleDamper | Single damper for ventilation and economizer, with airflow measurement station |
Revisions
-
December 15, 2022, by Jianjun Hu:
Removed the no-economizer option.
This is for issue 3139. -
August 1, 2020, by Jianjun Hu:
First implementation.