modelSupplyReturnTemperatureReset

Test model for the heating curve

Information

Example that demonstrates the use of the hot water temperature reset for a heating system. The parameters of the block heaCur are for a heating system with 60°C supply water temperature and 40°C return water temperature at an outside temperature of -10°C and a room temperature of 20°C. The offset for the temperature reset is 8 Kelvin, i.e., above 12°C outside temperature, there is no heating load. The figure below shows the computed supply and return water temperatures.

Supply and return water temperatures.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.Utilities.SetPoints.SupplyReturnTemperatureResetheaCurCompute the supply and return set point of heating systems with varying outdoor temperature
Buildings.Controls.OBC.CDL.Reals.Sources.RampTOutOutdoor temperature varying from -10 degC to 30 degC
Buildings.Controls.OBC.Utilities.SetPoints.SupplyReturnTemperatureResetheaCur1Compute the supply and return set point of heating systems with changing room setpoint temperature
Buildings.Controls.OBC.CDL.Reals.Sources.PulseTRoo1Night set back from 20 degC to 15 degC
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTOut1Constant outdoor air temperature
Buildings.Controls.OBC.CDL.Reals.Sources.ConstantTRooRoom temperature 20 degC

Revisions

  • July 18, 2017, by Jianjun Hu:
    First implementation in CDL.