modelOptimalStartNoHeatingNoCooling

Validation model for the block OptimalStart for the case with no preheating nor precooling

Information

This models validates the block Buildings.Controls.OBC.Utilities.OptimalStart for the case when the optimal start is not turned on for preheating or precooling before the scheduled occupancy.

The results shows that the optimal start time tOpt remains zero and the optimal start on signal optOn remains false during the simulation.

Components

TypeNameDefaultDescription
Buildings.Controls.OBC.Utilities.OptimalStartoptStaOptimal start for both heating and cooling system
Modelica.Blocks.Continuous.IntegratorTRooRoom air temperature
Buildings.Controls.OBC.CDL.Reals.Sources.SinTOutBaseOutdoor dry bulb temperature, base component
Buildings.Controls.OBC.CDL.Reals.MultiplyByParameterUAOverall heat loss coefficient
Buildings.Controls.OBC.CDL.Reals.SubtractdTTemperature difference between zone and outdoor
Buildings.Controls.OBC.CDL.Reals.MultiplyByParameterQCooHeat extraction in the zone
Buildings.Controls.OBC.CDL.Conversions.BooleanToRealbooToRea1Convert Boolean to Real signal
Buildings.Controls.OBC.CDL.Reals.Addadd1Reset temperature from unoccupied to occupied for optimal start period
Buildings.Controls.OBC.CDL.Reals.PIDconPID1PI control for space cooling
Buildings.Controls.SetPoints.OccupancyScheduleoccSchDaily schedule
Buildings.Controls.OBC.CDL.Reals.MultiSummulSumSum heat gains
Buildings.Controls.OBC.CDL.Conversions.BooleanToRealbooToRea2Convert Boolean to Real signal
Buildings.Controls.OBC.CDL.Reals.Addadd2Reset temperature from unoccupied to occupied for optimal start period
Buildings.Controls.OBC.CDL.Reals.PIDconPIDPI control for space heating
Buildings.Controls.OBC.CDL.Reals.MultiplyByParameterQHeaHeat injection in the zone
Buildings.Controls.OBC.CDL.Reals.AddTOutOutdoor dry bulb temperature
Buildings.Controls.OBC.CDL.Reals.Sources.PulsepulRange of outdoor dry bulb temperature
Buildings.Controls.OBC.CDL.Conversions.BooleanToRealTSetHeaRoom temperature set point for heating
Buildings.Controls.OBC.CDL.Conversions.BooleanToRealTSetCooRoom temperature set point for cooling

Revisions

  • March 19, 2020, by Michael Wetter:
    Simplified setpoint implementation.
  • December 15, 2019, by Kun Zhang:
    First implementation.