recordHVAC

Set points for the HVAC system

Extends from Modelica.Icons.Record (Icon for records).

Information

Data records with design and control parameters for the building heating, cooling and domestic hot water load.

Parameters

TypeNameDefaultDescription
Modelica.Units.SI.ThermodynamicTemperatureTChiWatRet_nominalTChiWatSup_nominal + dTChiWat_nominalNominal chilled water return temperature
Modelica.Units.SI.ThermodynamicTemperatureTHeaWatRet_nominalTHeaWatSup_nominal - dTHeaWat_nominalNominal heating hot water supply temperature
Chilled water
Modelica.Units.SI.ThermodynamicTemperatureTChiWatSup_nominal7 + 273.15Nominal chilled water supply temperature
Modelica.Units.SI.TemperatureDifferencedTChiWat_nominal5Nominal chilled water temperature difference
Modelica.Units.SI.ThermodynamicTemperature[2,2]tabChiWatRes[16 + 273.15, 12 + 273.15; 27 + 273.15, TChiWatSup_nominal]Chilled water supply temperature reset schedule
Heating hot water
Modelica.Units.SI.ThermodynamicTemperatureTHeaWatSup_nominal60 + 273.15Nominal heating hot water supply temperature
Modelica.Units.SI.TemperatureDifferencedTHeaWat_nominal10Nominal heating hot water temperature difference
Modelica.Units.SI.ThermodynamicTemperature[2,2]tabHeaWatRes[-6.7 + 273.15, THeaWatSup_nominal; 16 + 273.15, 30 + 273.15]Heating hot water supply temperature reset schedule as a function of outdoor air temperature. Don't set below 30 as the isolation valve is open only at 30 degC
Domestic hot water
Modelica.Units.SI.ThermodynamicTemperatureTHotWatSupTan_nominal50 + 273.15Nominal domestic heating water supply temperature to the tank
Modelica.Units.SI.ThermodynamicTemperatureTHotWatSupFix_nominal45 + 273.15Nominal domestic hot water supply temperature to the fixture

Revisions

  • November 14, 2025, by Michael Wetter:
    First implementation.
    This is for #4354.