modelMultiplePumpsFlow
Validation of multiple pumps model with flow-controlled pump model
Extends from BaseClasses.PartialMultiplePumps (Base class for validating the multiple pumps model).
Information
This model validates Buildings.DHC.Plants.Combined.Subsystems.MultiplePumpsFlow by comparing an instance of that model with two instances of Buildings.Fluid.Movers.FlowControlled_m_flow connected in parallel. The two pumps are commanded On one after the other as they receive an increasing flow setpoint and work against a two-way modulating valve that gets progressively opened.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Integer | nPum (from PartialMultiplePumps) | 2 | Number of pumps |
| Modelica.Units.SI.MassFlowRate | m_flow_nominal (from PartialMultiplePumps) | nPum*mPum_flow_nominal | Circuit mass flow rate at design conditions |
| Modelica.Units.SI.Pressure | p_min (from PartialMultiplePumps) | 2E5 | Circuit minimum pressure |
| Modelica.Units.SI.PressureDifference | dp_nominal (from PartialMultiplePumps) | dpPum_nominal | Circuit total pressure drop at design conditions |
| Nominal condition | |||
| Modelica.Units.SI.MassFlowRate | mPum_flow_nominal (from PartialMultiplePumps) | 1 | Pump mass flow rate (each pump) |
| Modelica.Units.SI.PressureDifference | dpPum_nominal (from PartialMultiplePumps) | 1E5 | Pump head (each pump) |
Components
Revisions
-
February 24, 2023, by Antoine Gautier:
First implementation.