modelVAVReheatBox

Supply box of a VAV system with a hot water reheat coil

Extends from Modelica.Blocks.Icons.Block (Basic graphical layout of input/output block).

Information

Model for a VAV terminal box with a water reheat coil and exponential damper.

Parameters

TypeNameDefaultDescription
BooleanallowFlowReversaltrue= false to simplify equations, assuming, but not enforcing, no flow reversal
Modelica.Units.SI.MassFlowRatemCooAir_flow_nominalNominal air mass flow rate from cooling sizing calculations
Modelica.Units.SI.MassFlowRatemHeaAir_flow_nominalNominal air mass flow rate from heating sizing calculations
Modelica.Units.SI.MassFlowRatemHeaWat_flow_nominalQHea_flow_nominal/(cpWatLiq*(THeaWatInl_nominal - THeaWatOut_nominal))Nominal mass flow rate of hot water to reheat coil
Modelica.Units.SI.VolumeVRooRoom volume
Modelica.Units.SI.TemperatureTHeaWatInl_nominalReheat coil nominal inlet water temperature
Modelica.Units.SI.TemperatureTHeaWatOut_nominalReheat coil nominal outlet water temperature
Modelica.Units.SI.TemperatureTHeaAirInl_nominalInlet air nominal temperature into VAV box during heating
Modelica.Units.SI.TemperatureTHeaAirDis_nominalDischarge air temperature from VAV box during heating
Modelica.Units.SI.HeatFlowRateQHea_flow_nominalmHeaAir_flow_nominal*cpAir*(THeaAirDis_nominal - THeaAirInl_nominal)Nominal heating heat flow rate

Connectors

TypeNameDefaultDescription
Modelica.Fluid.Interfaces.FluidPort_aport_aAirFluid connector a1 (positive design flow direction is from port_a1 to port_b1)
Modelica.Fluid.Interfaces.FluidPort_aport_bAirFluid connector b (positive design flow direction is from port_a1 to port_b1)
Modelica.Blocks.Interfaces.RealInputyVAVSignal for VAV damper
Modelica.Blocks.Interfaces.RealOutputy_actualActual VAV damper position
Modelica.Blocks.Interfaces.RealOutputyVal_actualActual valve position
Modelica.Fluid.Interfaces.FluidPort_aport_aHeaWatHot water inlet port
Modelica.Fluid.Interfaces.FluidPort_bport_bHeaWatHot water outlet port
Modelica.Blocks.Interfaces.RealOutputTSupSupply Air Temperature
Modelica.Blocks.Interfaces.RealOutputVSup_flowSupply Air Volumetric Flow Rate
Modelica.Blocks.Interfaces.RealInputyHeaActuator position for heating valve (0: closed, 1: open)

Components

TypeNameDefaultDescription
Buildings.Fluid.Actuators.Dampers.ExponentialvavVAV box for room
Buildings.Fluid.HeatExchangers.DryCoilEffectivenessNTUterHeaReheat coil
Fluid.Sensors.TemperatureTwoPortsenTemSupply air temperature sensor
Fluid.Sensors.VolumeFlowRatesenVolFloSupply air volumetric flow rate sensor
Fluid.Actuators.Valves.TwoWayEqualPercentagevalValve for terminal heater
RealACHVSup_flow/VRoo*3600Air changes per hour

Contents

NameDescription
MediumAMedium model for air
MediumWMedium model for water

Revisions

  • January 27, 2023, by Jianjun Hu:
    Changed the pressure independent damper to exponential damper. This is for issue #3139.
  • December 20, 2021, by Michael Wetter:
    Changed parameter declarations for issue #2829.
  • August 24, 2021, by Michael Wetter:
    Changed model to include the hydraulic configurations of the cooling coil, heating coil and VAV terminal box.
    This is for issue #2594.
  • February 12, 2021, by Baptiste Ravache:
    First implementation, based on Buildings.Obsolete.Examples.VAVReheat.BaseClasses.VAVBranch
    This is for #2024.