recordElectricEIRChiller_Carrier_19XR_1157kW_5_62COP_VSD

ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD

A record of Buildings.Fluid.Chillers.Data.ElectricEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD,  !- Name
    1156900,                 !- Reference Capacity {W}
    5.62,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    21.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02801,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03186,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.19,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.19,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1156900
COP_nominal5.62
PLRMin0.19
PLRMinUnl0.19
PLRMax1.01
mEva_flow_nominal1000*0.02801
mCon_flow_nominal1000*0.03186
TEvaLvg_nominal273.15 + 5.56
TConEnt_nominal273.15 + 21.11
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 10.00
TConEntMin273.15 + 11.25
TConEntMax273.15 + 23.89
capFunT{1.076248E+00, 5.436724E-03, -3.893302E-04, -4.353310E-03, -2.402031E-04, 8.409080E-04}
EIRFunT{1.075567E+00, -3.893571E-02, 1.082499E-03, -5.782829E-03, 6.574492E-04, -5.302886E-04}
EIRFunPLR{1.608589E-01, -2.058215E-01, 1.043133E+00}
etaMotor1.0