recordElectricEIRChiller_Carrier_19XR_1403kW_7_09COP_VSD

ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD

A record of Buildings.Fluid.Chillers.Data.ElectricEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD,  !- Name
    1403100,                 !- Reference Capacity {W}
    7.09,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    12.78,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.03426,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04252,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.17,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.17,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1403100
COP_nominal7.09
PLRMin0.17
PLRMinUnl0.17
PLRMax1.03
mEva_flow_nominal1000*0.03426
mCon_flow_nominal1000*0.04252
TEvaLvg_nominal273.15 + 6.67
TConEnt_nominal273.15 + 12.78
TEvaLvgMin273.15 + 6.67
TEvaLvgMax273.15 + 12.22
TConEntMin273.15 + 12.78
TConEntMax273.15 + 23.89
capFunT{9.601814E-01, -3.596494E-03, -1.706786E-03, 6.272429E-03, -9.858212E-04, 2.611673E-03}
EIRFunT{1.098641E+00, -2.485880E-02, -6.240421E-05, -1.719488E-03, 4.887321E-04, 9.618075E-05}
EIRFunPLR{8.788698E-02, 2.678891E-01, 6.445180E-01}
etaMotor1.0