recordElectricEIRChiller_Trane_CVHF_2317kW_6_33COP_VSD
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD
A record of Buildings.Fluid.Chillers.Data.ElectricEIR.Generic.
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD, !- Name
2317400, !- Reference Capacity {W}
6.33, !- Reference COP {W/W}
5.56, !- Reference Leaving Chilled Water Temperature {C}
29.44, !- Reference Entering Condenser Fluid Temperature {C}
0.09085, !- Reference Chilled Water Flow Rate {m3/s}
0.11356, !- Reference Condenser Water Flow Rate {m3/s}
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.10, !- Minimum Part Load Ratio
1.04, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
0.10, !- Minimum Unloading Ratio
Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name
Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name
Condenser Side Inlet Node, !- Condenser Inlet Node Name
Condenser Side Outlet Node, !- Condenser Outlet Node Name
WaterCooled, !- Condenser Type
, !- Condenser Fan Power Ratio {W/W}
1.0, !- Compressor Motor Efficiency
2.0, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode
0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Attributes
| Name | Value |
|---|---|
| QEva_flow_nominal | -2317400 |
| COP_nominal | 6.33 |
| PLRMin | 0.10 |
| PLRMinUnl | 0.10 |
| PLRMax | 1.04 |
| mEva_flow_nominal | 1000*0.09085 |
| mCon_flow_nominal | 1000*0.11356 |
| TEvaLvg_nominal | 273.15 + 5.56 |
| TConEnt_nominal | 273.15 + 29.44 |
| TEvaLvgMin | 273.15 + 4.44 |
| TEvaLvgMax | 273.15 + 8.89 |
| TConEntMin | 273.15 + 12.78 |
| TConEntMax | 273.15 + 29.44 |
| capFunT | {7.277716E-01, 1.018101E-02, -6.282438E-04, 1.337701E-02, -5.050352E-04, 1.527259E-03} |
| EIRFunT | {3.502330E-01, -2.301510E-02, 5.749596E-04, 1.902421E-02, 3.109974E-04, -4.714517E-04} |
| EIRFunPLR | {9.861441E-02, 5.297727E-01, 3.707229E-01} |
| etaMotor | 1.0 |