recordElectricEIRChiller_Trane_RTHC_1066kW_5_73COP_Valve

ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve

A record of Buildings.Fluid.Chillers.Data.ElectricEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve,  !- Name
    1065500,                 !- Reference Capacity {W}
    5.73,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    25.28,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05142,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04416,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.30,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.30,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1065500
COP_nominal5.73
PLRMin0.30
PLRMinUnl0.30
PLRMax1.01
mEva_flow_nominal1000*0.05142
mCon_flow_nominal1000*0.04416
TEvaLvg_nominal273.15 + 5.56
TConEnt_nominal273.15 + 25.28
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 10.00
TConEntMin273.15 + 20.07
TConEntMax273.15 + 25.28
capFunT{1.062396E+00, 4.575299E-02, 2.802795E-04, -8.802343E-03, -3.127891E-05, -5.937227E-04}
EIRFunT{9.003080E-01, 3.783201E-03, 9.815780E-04, -4.051727E-02, 2.037095E-03, -1.619326E-03}
EIRFunPLR{1.007344E-01, 1.119205E+00, -2.173230E-01}
etaMotor1.0