recordElectricEIRChiller_York_YK_4477kW_6_64COP_Vanes

ElectricEIRChiller York YK 4477kW/6.64COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 4477kW/6.64COP/Vanes,  !- Name
    4476700,                 !- Reference Capacity {W}
    6.64,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.67,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 4477kW/6.64COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 4477kW/6.64COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 4477kW/6.64COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.41,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.41,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-4476700
COP_nominal6.64
PLRMin0.41
PLRMinUnl0.41
PLRMax1.06
mEva_flow_nominal1000*0.19558
mCon_flow_nominal1000*0.24605
TEvaLvg_nominal273.15 + 6.67
TConEnt_nominal273.15 + 26.67
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 7.78
TConEntMin273.15 + 12.78
TConEntMax273.15 + 26.67
capFunT{4.844230E-01, -9.879643E-02, -2.516527E-03, 1.144722E-01, -5.101526E-03, 1.022861E-02}
EIRFunT{4.264570E-01, -3.391606E-02, -1.991396E-03, 5.032090E-02, -1.140771E-03, 1.814692E-03}
EIRFunPLR{2.767206E-01, 1.074393E-01, 6.145706E-01}
etaMotor1.0