recordElectricEIRChiller_York_YK_4969kW_7_14COP_Vanes

ElectricEIRChiller York YK 4969kW/7.14COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller York YK 4969kW/7.14COP/Vanes,  !- Name
    4969000,                 !- Reference Capacity {W}
    7.14,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    26.11,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.17665,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.26498,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YK 4969kW/7.14COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YK 4969kW/7.14COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YK 4969kW/7.14COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.16,                    !- Minimum Part Load Ratio
    1.07,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.16,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-4969000
COP_nominal7.14
PLRMin0.16
PLRMinUnl0.16
PLRMax1.07
mEva_flow_nominal1000*0.17665
mCon_flow_nominal1000*0.26498
TEvaLvg_nominal273.15 + 6.67
TConEnt_nominal273.15 + 26.11
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConEntMin273.15 + 12.78
TConEntMax273.15 + 29.44
capFunT{7.817577E-01, -1.012013E-01, -1.584389E-03, 7.928475E-02, -3.674093E-03, 7.999392E-03}
EIRFunT{7.382162E-01, -5.847442E-02, 1.117191E-03, 2.168089E-02, -2.189722E-04, 1.036877E-03}
EIRFunPLR{2.259512E-01, 2.320151E-01, 5.423771E-01}
etaMotor1.0