recordElectricEIRChiller_York_YT_1055kW_5_96COP_Vanes

ElectricEIRChiller York YT 1055kW/5.96COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1055kW/5.96COP/Vanes,  !- Name
    1055000,                 !- Reference Capacity {W}
    5.96,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.44,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.02839,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05678,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1055kW/5.96COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1055kW/5.96COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1055kW/5.96COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1055000
COP_nominal5.96
PLRMin0.10
PLRMinUnl0.10
PLRMax1.05
mEva_flow_nominal1000*0.02839
mCon_flow_nominal1000*0.05678
TEvaLvg_nominal273.15 + 6.67
TConEnt_nominal273.15 + 29.44
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConEntMin273.15 + 12.78
TConEntMax273.15 + 35.00
capFunT{1.785912E-01, -5.900023E-02, -5.946963E-04, 9.297889E-02, -2.841024E-03, 4.974221E-03}
EIRFunT{5.245110E-01, -2.850126E-02, 8.034720E-04, 1.893133E-02, 1.151629E-04, -9.340642E-05}
EIRFunPLR{2.619878E-01, 2.393605E-01, 4.988306E-01}
etaMotor1.0