recordElectricEIRChiller_York_YT_1368kW_7_35COP_VSD

ElectricEIRChiller York YT 1368kW/7.35COP/VSD

A record of Buildings.Fluid.Chillers.Data.ElectricEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1368kW/7.35COP/VSD,  !- Name
    1367900,                 !- Reference Capacity {W}
    7.35,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.05047,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.07571,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1368kW/7.35COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1368kW/7.35COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1368kW/7.35COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1367900
COP_nominal7.35
PLRMin0.10
PLRMinUnl0.10
PLRMax1.03
mEva_flow_nominal1000*0.05047
mCon_flow_nominal1000*0.07571
TEvaLvg_nominal273.15 + 5.56
TConEnt_nominal273.15 + 23.89
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConEntMin273.15 + 12.78
TConEntMax273.15 + 29.44
capFunT{3.832184E-01, -3.265439E-02, -3.392654E-03, 8.580180E-02, -3.513013E-03, 6.528440E-03}
EIRFunT{3.227543E-01, -1.415418E-02, -5.090650E-03, 4.606511E-02, -8.769578E-04, 2.600343E-03}
EIRFunPLR{9.483562E-02, 1.521114E-01, 7.543027E-01}
etaMotor1.0