recordElectricEIRChiller_York_YT_1495kW_7_51COP_VSD

ElectricEIRChiller York YT 1495kW/7.51COP/VSD

A record of Buildings.Fluid.Chillers.Data.ElectricEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:EIR,
    ElectricEIRChiller York YT 1495kW/7.51COP/VSD,  !- Name
    1494500,                 !- Reference Capacity {W}
    7.51,                    !- Reference COP {W/W}
    7.22,                    !- Reference Leaving Chilled Water Temperature {C}
    23.89,                   !- Reference Entering Condenser Fluid Temperature {C}
    0.0429,                  !- Reference Chilled Water Flow Rate {m3/s}
    0.06719,                 !- Reference Condenser Water Flow Rate {m3/s}
    ElectricEIRChiller York YT 1495kW/7.51COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ElectricEIRChiller York YT 1495kW/7.51COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ElectricEIRChiller York YT 1495kW/7.51COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.11,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.11,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    WaterCooled,             !- Condenser Type
    ,                        !- Condenser Fan Power Ratio {W/W}
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1494500
COP_nominal7.51
PLRMin0.11
PLRMinUnl0.11
PLRMax1.05
mEva_flow_nominal1000*0.0429
mCon_flow_nominal1000*0.06719
TEvaLvg_nominal273.15 + 7.22
TConEnt_nominal273.15 + 23.89
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 8.89
TConEntMin273.15 + 12.78
TConEntMax273.15 + 35.00
capFunT{1.051921E+00, -1.632255E-01, 1.149042E-02, 5.463515E-02, -1.579985E-03, 1.628246E-03}
EIRFunT{7.106985E-01, -2.087623E-01, 9.421379E-03, 8.491925E-02, -1.260820E-03, 1.125512E-03}
EIRFunPLR{1.517470E-01, -1.577252E-01, 1.005197E+00}
etaMotor1.0