recordReformEIRChiller_Carrier_19EX_4997kW_6_40COP_Vanes

ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes,  !- Name
    4997200,                 !- Reference Capacity {W}
    6.40,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    32.28,                   !- Reference Leaving Condenser Water Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.40,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.40,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-4997200
COP_nominal6.40
PLRMin0.40
PLRMinUnl0.40
PLRMax1.04
mEva_flow_nominal1000*0.19558
mCon_flow_nominal1000*0.24605
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 32.28
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 7.78
TConLvgMin273.15 + 17.18
TConLvgMax273.15 + 32.28
capFunT{-2.686142E-01, -4.640249E-02, -7.791139E-03, 1.116057E-01, -3.040750E-03, 6.823316E-03}
EIRFunT{7.502378E-01, -8.546174E-03, 3.952892E-03, -7.194001E-03, 8.754798E-04, -2.523240E-03}
EIRFunPLR{6.778244E-01, -1.674571E-02, -1.069925E-05, 2.261951E-01, -1.572357E-02, 1.714268E-02, 0.000000E+00, 1.072291E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0