recordReformEIRChiller_Carrier_19XL_1797kW_5_69COP_Vanes

ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes,  !- Name
    1797000,                 !- Reference Capacity {W}
    5.69,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    34.67,                   !- Reference Leaving Condenser Water Temperature {C}
    0.07737,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09672,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.39,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.39,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1797000
COP_nominal5.69
PLRMin0.39
PLRMinUnl0.39
PLRMax1.01
mEva_flow_nominal1000*0.07737
mCon_flow_nominal1000*0.09672
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 34.67
TEvaLvgMin273.15 + 6.67
TEvaLvgMax273.15 + 10.00
TConLvgMin273.15 + 26.59
TConLvgMax273.15 + 34.91
capFunT{9.173209E-01, 4.990036E-02, -1.196031E-03, -2.024380E-03, -3.141698E-05, -3.752508E-04}
EIRFunT{1.079738E+00, -4.447776E-02, 1.617276E-03, 8.485662E-04, 8.268362E-05, 5.543283E-05}
EIRFunPLR{5.147565E+00, -1.604653E-01, 2.139293E-05, -3.215408E+00, -1.636618E+00, 1.592219E-01, 0.000000E+00, 7.224656E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0