recordReformEIRChiller_Carrier_19XR_897kW_6_23COP_VSD

ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD,  !- Name
    896700,                  !- Reference Capacity {W}
    6.23,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    29.49,                   !- Reference Leaving Condenser Water Temperature {C}
    0.06782,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.04442,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-896700
COP_nominal6.23
PLRMin0.20
PLRMinUnl0.20
PLRMax1.02
mEva_flow_nominal1000*0.06782
mCon_flow_nominal1000*0.04442
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 29.49
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 10.00
TConLvgMin273.15 + 18.61
TConLvgMax273.15 + 30.29
capFunT{8.691024E-01, 2.885812E-02, 1.795420E-04, 4.868722E-03, -3.207870E-04, 3.825044E-04}
EIRFunT{8.640049E-01, 5.766109E-03, 1.197122E-03, -2.312809E-03, 4.642915E-04, -1.375629E-03}
EIRFunPLR{9.617997E-01, -8.158350E-02, -5.841564E-06, 1.169179E+00, -1.600491E+00, 8.176055E-02, 0.000000E+00, 4.684331E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0