recordReformEIRChiller_McQuay_PEH_703kW_7_03COP_Vanes

ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes,  !- Name
    703300,                  !- Reference Capacity {W}
    7.03,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    29.40,                   !- Reference Leaving Condenser Water Temperature {C}
    0.02019,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.02902,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-703300
COP_nominal7.03
PLRMin0.10
PLRMinUnl0.10
PLRMax1.02
mEva_flow_nominal1000*0.02019
mCon_flow_nominal1000*0.02902
TEvaLvg_nominal273.15 + 5.56
TConLvg_nominal273.15 + 29.40
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 20.28
TConLvgMax273.15 + 31.25
capFunT{-1.336180E-01, 6.473161E-02, -1.240446E-02, 9.425649E-02, -2.958871E-03, 5.765503E-03}
EIRFunT{8.177961E-01, -1.756394E-01, 2.510719E-03, 2.677783E-02, -4.926551E-04, 4.559008E-03}
EIRFunPLR{2.342644E+00, -1.060883E-01, 2.710155E-04, -2.289108E+00, 3.338339E+00, 9.221626E-02, 0.000000E+00, -2.217954E+00, 0.000000E+00, 0.000000E+00}
etaMotor1.0