recordReformEIRChiller_Trane_CGWD_207kW_3_99COP_None

ReformEIRChiller Trane CGWD 207kW/3.99COP/None

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Trane CGWD 207kW/3.99COP/None,  !- Name
    207400,                  !- Reference Capacity {W}
    3.99,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    35.00,                   !- Reference Leaving Condenser Water Temperature {C}
    0.00898,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.01122,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Trane CGWD 207kW/3.99COP/None CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Trane CGWD 207kW/3.99COP/None EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Trane CGWD 207kW/3.99COP/None EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.25,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.25,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-207400
COP_nominal3.99
PLRMin0.25
PLRMinUnl0.25
PLRMax1.01
mEva_flow_nominal1000*0.00898
mCon_flow_nominal1000*0.01122
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 35.00
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 10.00
TConLvgMin273.15 + 29.37
TConLvgMax273.15 + 40.94
capFunT{9.585465E-01, 3.516870E-02, 1.246624E-04, -2.745559E-03, -5.000232E-05, -1.723494E-04}
EIRFunT{7.327001E-01, -8.343605E-03, 6.385302E-04, -3.037535E-03, 4.849529E-04, -8.358498E-04}
EIRFunPLR{7.086284E-02, 2.787561E-03, -8.917038E-06, 2.309734E-01, 1.250442E+00, -2.161029E-03, 0.000000E+00, -5.630094E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0