recordReformEIRChiller_Trane_RTHB_531kW_4_83COP_Valve

ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve,  !- Name
    531000,                  !- Reference Capacity {W}
    4.83,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    33.61,                   !- Reference Leaving Condenser Water Temperature {C}
    0.0135,                  !- Reference Chilled Water Flow Rate {m3/s}
    0.01577,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.30,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.30,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-531000
COP_nominal4.83
PLRMin0.30
PLRMinUnl0.30
PLRMax1.01
mEva_flow_nominal1000*0.0135
mCon_flow_nominal1000*0.01577
TEvaLvg_nominal273.15 + 5.56
TConLvg_nominal273.15 + 33.61
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 10.00
TConLvgMin273.15 + 25.39
TConLvgMax273.15 + 34.83
capFunT{9.079958E-01, 1.147213E-02, 8.474223E-04, 7.750840E-03, -2.955319E-04, 3.620562E-04}
EIRFunT{3.048223E-01, 1.023123E-02, 2.011952E-04, 1.296369E-02, 4.087926E-04, -1.374337E-03}
EIRFunPLR{4.560311E+00, -2.031290E-01, 8.212225E-05, -4.899042E+00, 5.087775E+00, 1.981069E-01, 0.000000E+00, -3.673772E+00, 0.000000E+00, 0.000000E+00}
etaMotor1.0