recordReformEIRChiller_Trane_RTHB_538kW_5_12COP_Valve

ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve,  !- Name
    538000,                  !- Reference Capacity {W}
    5.12,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    31.75,                   !- Reference Leaving Condenser Water Temperature {C}
    0.01375,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.01956,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.30,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.30,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-538000
COP_nominal5.12
PLRMin0.30
PLRMinUnl0.30
PLRMax1.01
mEva_flow_nominal1000*0.01375
mCon_flow_nominal1000*0.01956
TEvaLvg_nominal273.15 + 5.56
TConLvg_nominal273.15 + 31.75
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 10.00
TConLvgMin273.15 + 23.52
TConLvgMax273.15 + 32.74
capFunT{9.326777E-01, 2.745642E-02, 3.991103E-04, 1.073891E-03, -1.335614E-04, 1.399941E-05}
EIRFunT{4.761769E-01, -3.860230E-03, 6.543433E-04, 7.029128E-03, 4.964676E-04, -1.113233E-03}
EIRFunPLR{2.185505E+00, -9.516501E-02, 2.591946E-05, -1.849602E+00, 2.059148E+00, 9.366870E-02, 0.000000E+00, -1.373917E+00, 0.000000E+00, 0.000000E+00}
etaMotor1.0