recordReformEIRChiller_Trane_RTWA_383kW_4_17COP_Valve

ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve,  !- Name
    383300,                  !- Reference Capacity {W}
    4.17,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    34.95,                   !- Reference Leaving Condenser Water Temperature {C}
    0.0165,                  !- Reference Chilled Water Flow Rate {m3/s}
    0.02063,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.25,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.25,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-383300
COP_nominal4.17
PLRMin0.25
PLRMinUnl0.25
PLRMax1.01
mEva_flow_nominal1000*0.0165
mCon_flow_nominal1000*0.02063
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 34.95
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 29.19
TConLvgMax273.15 + 40.69
capFunT{1.005026E+00, 3.896773E-02, 9.270374E-05, -4.346837E-03, -4.961570E-05, -2.401448E-04}
EIRFunT{6.171417E-01, -4.530431E-03, 1.108471E-03, -3.373738E-04, 5.176833E-04, -1.098531E-03}
EIRFunPLR{-1.660765E+00, 1.117605E-01, 4.971509E-06, -3.472160E-02, 3.399869E+00, -1.121089E-01, 0.000000E+00, -6.984388E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0