recordReformEIRChiller_York_YK_1259kW_6_45COP_Vanes

ReformEIRChiller York YK 1259kW/6.45COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 1259kW/6.45COP/Vanes,  !- Name
    1258900,                 !- Reference Capacity {W}
    6.45,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    32.24,                   !- Reference Leaving Condenser Water Temperature {C}
    0.02631,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06246,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 1259kW/6.45COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 1259kW/6.45COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 1259kW/6.45COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.18,                    !- Minimum Part Load Ratio
    1.02,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.18,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1258900
COP_nominal6.45
PLRMin0.18
PLRMinUnl0.18
PLRMax1.02
mEva_flow_nominal1000*0.02631
mCon_flow_nominal1000*0.06246
TEvaLvg_nominal273.15 + 8.89
TConLvg_nominal273.15 + 32.24
TEvaLvgMin273.15 + 7.22
TEvaLvgMax273.15 + 12.78
TConLvgMin273.15 + 19.63
TConLvgMax273.15 + 32.83
capFunT{7.917669E-01, 7.718144E-02, -1.868147E-03, 2.168367E-02, -9.454040E-04, -1.251512E-04}
EIRFunT{1.207755E+00, 2.704147E-02, -1.882949E-05, -5.234106E-02, 1.851447E-03, -2.375891E-03}
EIRFunPLR{-3.830726E-01, 3.222162E-02, 7.399276E-05, 3.649000E-01, 1.497231E+00, -3.597905E-02, 0.000000E+00, -4.321713E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0