recordReformEIRChiller_York_YK_1997kW_7_24COP_Vanes

ReformEIRChiller York YK 1997kW/7.24COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 1997kW/7.24COP/Vanes,  !- Name
    1997400,                 !- Reference Capacity {W}
    7.24,                    !- Reference COP {W/W}
    8.89,                    !- Reference Leaving Chilled Water Temperature {C}
    31.89,                   !- Reference Leaving Condenser Water Temperature {C}
    0.04397,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.1041,                  !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 1997kW/7.24COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 1997kW/7.24COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 1997kW/7.24COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.18,                    !- Minimum Part Load Ratio
    1.07,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.18,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1997400
COP_nominal7.24
PLRMin0.18
PLRMinUnl0.18
PLRMax1.07
mEva_flow_nominal1000*0.04397
mCon_flow_nominal1000*0.1041
TEvaLvg_nominal273.15 + 8.89
TConLvg_nominal273.15 + 31.89
TEvaLvgMin273.15 + 7.22
TEvaLvgMax273.15 + 12.78
TConLvgMin273.15 + 19.16
TConLvgMax273.15 + 32.70
capFunT{1.039493E+00, 1.593009E-01, -3.989073E-03, -3.812180E-02, 2.881779E-04, -7.520087E-04}
EIRFunT{1.550813E-01, 1.022114E-01, -6.511170E-04, -1.241272E-02, 1.514358E-03, -4.090377E-03}
EIRFunPLR{1.838759E-01, -1.009515E-02, 1.677624E-04, 9.181489E-01, -2.434151E-02, 1.727052E-03, 0.000000E+00, 2.527075E-02, 0.000000E+00, 0.000000E+00}
etaMotor1.0