recordReformEIRChiller_York_YK_2201kW_6_69COP_Vanes

ReformEIRChiller York YK 2201kW/6.69COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 2201kW/6.69COP/Vanes,  !- Name
    2201400,                 !- Reference Capacity {W}
    6.69,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    31.44,                   !- Reference Leaving Condenser Water Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 2201kW/6.69COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 2201kW/6.69COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 2201kW/6.69COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.14,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.14,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-2201400
COP_nominal6.69
PLRMin0.14
PLRMinUnl0.14
PLRMax1.05
mEva_flow_nominal1000*0.07571
mCon_flow_nominal1000*0.11356
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 31.44
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 21.11
TConLvgMax273.15 + 34.92
capFunT{-2.132698E-01, -9.712289E-02, -7.445252E-03, 1.333444E-01, -3.971284E-03, 9.247854E-03}
EIRFunT{8.761500E-01, 2.513467E-02, -8.565300E-04, -1.383243E-02, 6.968311E-04, -1.236275E-03}
EIRFunPLR{3.515554E-03, 3.070346E-02, -1.198496E-08, -5.568236E-01, 1.810053E+00, -3.070120E-02, 0.000000E+00, -2.564025E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0