recordReformEIRChiller_York_YK_2412kW_5_58COP_Vanes

ReformEIRChiller York YK 2412kW/5.58COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 2412kW/5.58COP/Vanes,  !- Name
    2412400,                 !- Reference Capacity {W}
    5.58,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    32.10,                   !- Reference Leaving Condenser Water Temperature {C}
    0.09085,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.11356,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 2412kW/5.58COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 2412kW/5.58COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 2412kW/5.58COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.12,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.12,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-2412400
COP_nominal5.58
PLRMin0.12
PLRMinUnl0.12
PLRMax1.01
mEva_flow_nominal1000*0.09085
mCon_flow_nominal1000*0.11356
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 32.10
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 21.30
TConLvgMax273.15 + 35.78
capFunT{6.042244E-01, -5.282819E-03, -1.993748E-04, 2.972266E-02, -8.288016E-04, 1.587869E-03}
EIRFunT{3.175495E-01, -2.563749E-02, 1.177157E-03, 3.422467E-02, -2.556973E-04, -1.034934E-04}
EIRFunPLR{-8.659288E-02, 4.280342E-02, 4.027354E-05, -8.726041E-01, 3.432389E+00, -4.514744E-02, 0.000000E+00, -1.440179E+00, 0.000000E+00, 0.000000E+00}
etaMotor1.0