recordReformEIRChiller_York_YK_4396kW_6_63COP_Vanes

ReformEIRChiller York YK 4396kW/6.63COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 4396kW/6.63COP/Vanes,  !- Name
    4395800,                 !- Reference Capacity {W}
    6.63,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    31.58,                   !- Reference Leaving Condenser Water Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 4396kW/6.63COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 4396kW/6.63COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 4396kW/6.63COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.41,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.41,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-4395800
COP_nominal6.63
PLRMin0.41
PLRMinUnl0.41
PLRMax1.05
mEva_flow_nominal1000*0.19558
mCon_flow_nominal1000*0.24605
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 31.58
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 7.78
TConLvgMin273.15 + 18.53
TConLvgMax273.15 + 31.58
capFunT{-7.935103E-01, -1.859711E-01, -1.136209E-02, 2.223615E-01, -6.910739E-03, 1.608112E-02}
EIRFunT{3.992978E-01, -5.787211E-02, 4.974140E-04, 4.071879E-02, -5.579169E-04, 9.811292E-04}
EIRFunPLR{3.551587E-01, -8.505111E-03, 1.396120E-04, 5.048375E-01, -1.447328E-01, 1.902634E-03, 0.000000E+00, 3.599323E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0