recordReformEIRChiller_York_YK_4515kW_6_22COP_Vanes

ReformEIRChiller York YK 4515kW/6.22COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 4515kW/6.22COP/Vanes,  !- Name
    4515400,                 !- Reference Capacity {W}
    6.22,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    31.76,                   !- Reference Leaving Condenser Water Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 4515kW/6.22COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 4515kW/6.22COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 4515kW/6.22COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.40,                    !- Minimum Part Load Ratio
    1.03,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.40,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-4515400
COP_nominal6.22
PLRMin0.40
PLRMinUnl0.40
PLRMax1.03
mEva_flow_nominal1000*0.19558
mCon_flow_nominal1000*0.24605
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 31.76
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 7.78
TConLvgMin273.15 + 17.15
TConLvgMax273.15 + 31.76
capFunT{2.075078E-01, -1.981043E-02, -2.892690E-03, 5.881989E-02, -1.521616E-03, 3.461206E-03}
EIRFunT{6.011575E-01, 1.661031E-02, -2.137279E-06, 4.501265E-03, 5.130434E-04, -1.786025E-03}
EIRFunPLR{7.069612E-01, -1.915921E-02, 3.601682E-04, -2.561145E-01, 1.177821E+00, 2.539786E-03, 0.000000E+00, -4.447869E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0