recordReformEIRChiller_York_YK_4537kW_6_28COP_Vanes

ReformEIRChiller York YK 4537kW/6.28COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 4537kW/6.28COP/Vanes,  !- Name
    4536500,                 !- Reference Capacity {W}
    6.28,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    31.78,                   !- Reference Leaving Condenser Water Temperature {C}
    0.19558,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.24605,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 4537kW/6.28COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 4537kW/6.28COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 4537kW/6.28COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.40,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.40,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-4536500
COP_nominal6.28
PLRMin0.40
PLRMinUnl0.40
PLRMax1.04
mEva_flow_nominal1000*0.19558
mCon_flow_nominal1000*0.24605
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 31.78
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 7.78
TConLvgMin273.15 + 19.77
TConLvgMax273.15 + 31.78
capFunT{1.769339E-01, 8.033367E-04, -1.299649E-02, 1.160227E-01, -4.192731E-03, 9.339837E-03}
EIRFunT{8.920183E-01, -1.501518E-02, 1.467430E-03, -1.261335E-02, 8.431355E-04, -1.426299E-03}
EIRFunPLR{1.718938E-01, 6.637990E-03, 1.666991E-05, 1.634153E-01, 9.517270E-01, -7.705773E-03, 0.000000E+00, -2.724674E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0