recordReformEIRChiller_York_YK_4969kW_7_14COP_Vanes

ReformEIRChiller York YK 4969kW/7.14COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 4969kW/7.14COP/Vanes,  !- Name
    4969000,                 !- Reference Capacity {W}
    7.14,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    31.23,                   !- Reference Leaving Condenser Water Temperature {C}
    0.17665,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.26498,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 4969kW/7.14COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 4969kW/7.14COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 4969kW/7.14COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.16,                    !- Minimum Part Load Ratio
    1.07,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.16,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-4969000
COP_nominal7.14
PLRMin0.16
PLRMinUnl0.16
PLRMax1.07
mEva_flow_nominal1000*0.17665
mCon_flow_nominal1000*0.26498
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 31.23
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 18.57
TConLvgMax273.15 + 34.55
capFunT{2.811615E-03, -1.788883E-01, -4.640550E-03, 1.472024E-01, -4.625224E-03, 1.108352E-02}
EIRFunT{6.916913E-01, -4.760980E-02, 1.310678E-03, 1.226839E-02, 1.561278E-04, 1.331849E-04}
EIRFunPLR{3.289463E-01, 6.642124E-03, -2.636011E-05, -4.910925E-01, 1.639401E+00, -5.204880E-03, 0.000000E+00, -4.960251E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0