recordReformEIRChiller_York_YK_5465kW_6_94COP_Vanes

ReformEIRChiller York YK 5465kW/6.94COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YK 5465kW/6.94COP/Vanes,  !- Name
    5464900,                 !- Reference Capacity {W}
    6.94,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    31.56,                   !- Reference Leaving Condenser Water Temperature {C}
    0.18296,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.27444,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YK 5465kW/6.94COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YK 5465kW/6.94COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YK 5465kW/6.94COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.14,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.14,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-5464900
COP_nominal6.94
PLRMin0.14
PLRMinUnl0.14
PLRMax1.06
mEva_flow_nominal1000*0.18296
mCon_flow_nominal1000*0.27444
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 31.56
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 21.03
TConLvgMax273.15 + 34.99
capFunT{-1.004987E+00, -2.020843E-01, -5.768143E-03, 2.096972E-01, -5.537991E-03, 1.195948E-02}
EIRFunT{5.844853E-01, -4.786810E-02, 7.315110E-04, 2.167930E-02, -8.850313E-05, 5.184829E-04}
EIRFunPLR{8.903067E-01, -1.058205E-03, 4.591261E-05, -2.096863E+00, 3.368956E+00, -1.380690E-03, 0.000000E+00, -1.130250E+00, 0.000000E+00, 0.000000E+00}
etaMotor1.0