recordReformEIRChiller_York_YS_1758kW_5_84COP_Valve

ReformEIRChiller York YS 1758kW/5.84COP/Valve

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YS 1758kW/5.84COP/Valve,  !- Name
    1758300,                 !- Reference Capacity {W}
    5.84,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    34.65,                   !- Reference Leaving Condenser Water Temperature {C}
    0.07571,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.09464,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YS 1758kW/5.84COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YS 1758kW/5.84COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YS 1758kW/5.84COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.20,                    !- Minimum Part Load Ratio
    1.05,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.20,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1758300
COP_nominal5.84
PLRMin0.20
PLRMinUnl0.20
PLRMax1.05
mEva_flow_nominal1000*0.07571
mCon_flow_nominal1000*0.09464
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 34.65
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 17.74
TConLvgMax273.15 + 39.72
capFunT{6.348511E-01, -2.523830E-02, -1.840036E-03, 3.830396E-02, -9.961929E-04, 1.906565E-03}
EIRFunT{7.492787E-01, 1.912506E-02, 1.303486E-03, -1.981703E-02, 1.003666E-03, -1.936814E-03}
EIRFunPLR{-1.522140E-01, 2.440667E-02, -5.691764E-05, 4.875495E-01, 7.490485E-01, -2.093720E-02, 0.000000E+00, -1.319819E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0