recordReformEIRChiller_York_YS_781kW_5_42COP_Valve

ReformEIRChiller York YS 781kW/5.42COP/Valve

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YS 781kW/5.42COP/Valve,  !- Name
    780700,                  !- Reference Capacity {W}
    5.42,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    35.29,                   !- Reference Leaving Condenser Water Temperature {C}
    0.01893,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.03785,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YS 781kW/5.42COP/Valve CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YS 781kW/5.42COP/Valve EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YS 781kW/5.42COP/Valve EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.09,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.09,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-780700
COP_nominal5.42
PLRMin0.09
PLRMinUnl0.09
PLRMax1.01
mEva_flow_nominal1000*0.01893
mCon_flow_nominal1000*0.03785
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 35.29
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 21.31
TConLvgMax273.15 + 41.08
capFunT{1.033403E+00, 3.515774E-02, 4.288264E-04, -5.737406E-03, -2.647149E-05, -2.222927E-04}
EIRFunT{4.008316E-01, -6.141937E-03, 8.113800E-04, 5.982224E-03, 5.345503E-04, -1.142919E-03}
EIRFunPLR{5.519460E-01, -1.406889E-02, 3.843199E-06, 7.950267E-02, 8.798848E-01, 1.379480E-02, 0.000000E+00, -5.070156E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0