recordReformEIRChiller_York_YT_1048kW_6_06COP_Vanes

ReformEIRChiller York YT 1048kW/6.06COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YT 1048kW/6.06COP/Vanes,  !- Name
    1047900,                 !- Reference Capacity {W}
    6.06,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    34.59,                   !- Reference Leaving Condenser Water Temperature {C}
    0.04542,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05678,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YT 1048kW/6.06COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YT 1048kW/6.06COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YT 1048kW/6.06COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1047900
COP_nominal6.06
PLRMin0.10
PLRMinUnl0.10
PLRMax1.06
mEva_flow_nominal1000*0.04542
mCon_flow_nominal1000*0.05678
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 34.59
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 20.43
TConLvgMax273.15 + 39.72
capFunT{5.846663E-01, 1.059863E-02, -5.058695E-03, 3.006085E-02, -9.364366E-04, 2.597223E-03}
EIRFunT{7.745270E-01, -3.256346E-02, 2.992117E-03, -5.274460E-03, 6.701377E-04, -1.236258E-03}
EIRFunPLR{5.753623E-01, -1.409335E-02, -5.983885E-06, 6.063425E-01, -3.090569E-01, 1.412467E-02, 0.000000E+00, 1.296066E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0