recordReformEIRChiller_York_YT_1055kW_5_96COP_Vanes

ReformEIRChiller York YT 1055kW/5.96COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YT 1055kW/5.96COP/Vanes,  !- Name
    1055000,                 !- Reference Capacity {W}
    5.96,                    !- Reference COP {W/W}
    6.67,                    !- Reference Leaving Chilled Water Temperature {C}
    34.63,                   !- Reference Leaving Condenser Water Temperature {C}
    0.02839,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.05678,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YT 1055kW/5.96COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YT 1055kW/5.96COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YT 1055kW/5.96COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.06,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1055000
COP_nominal5.96
PLRMin0.10
PLRMinUnl0.10
PLRMax1.06
mEva_flow_nominal1000*0.02839
mCon_flow_nominal1000*0.05678
TEvaLvg_nominal273.15 + 6.67
TConLvg_nominal273.15 + 34.63
TEvaLvgMin273.15 + 4.44
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 17.24
TConLvgMax273.15 + 39.89
capFunT{-2.707500E-01, -6.904583E-02, -2.862217E-03, 1.116660E-01, -2.741006E-03, 5.573759E-03}
EIRFunT{5.864611E-01, -1.981483E-02, 1.189656E-03, 4.468905E-03, 4.366968E-04, -7.679079E-04}
EIRFunPLR{2.585491E-01, 8.250769E-03, -3.231494E-05, -8.921620E-02, 1.025668E+00, -6.495267E-03, 0.000000E+00, -2.179388E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0