recordReformEIRChiller_York_YT_1663kW_9_34COP_Vanes

ReformEIRChiller York YT 1663kW/9.34COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YT 1663kW/9.34COP/Vanes,  !- Name
    1663300,                 !- Reference Capacity {W}
    9.34,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    18.45,                   !- Reference Leaving Condenser Water Temperature {C}
    0.04139,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.0776,                  !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YT 1663kW/9.34COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YT 1663kW/9.34COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YT 1663kW/9.34COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.17,                    !- Minimum Part Load Ratio
    1.04,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.17,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1663300
COP_nominal9.34
PLRMin0.17
PLRMinUnl0.17
PLRMax1.04
mEva_flow_nominal1000*0.04139
mCon_flow_nominal1000*0.0776
TEvaLvg_nominal273.15 + 5.56
TConLvg_nominal273.15 + 18.45
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 8.89
TConLvgMin273.15 + 18.45
TConLvgMax273.15 + 34.43
capFunT{6.972683E-01, -9.692349E-02, 4.846738E-03, 5.523481E-02, -1.995272E-03, 3.533436E-03}
EIRFunT{9.477120E-01, -3.913396E-02, 2.408597E-03, 6.703909E-03, 5.744537E-04, -1.084620E-03}
EIRFunPLR{3.131373E-01, -3.438844E-03, -2.715303E-06, 1.918294E-01, 7.024552E-01, 3.301543E-03, 0.000000E+00, -2.040731E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0