recordReformEIRChiller_York_YT_1758kW_5_96COP_Vanes

ReformEIRChiller York YT 1758kW/5.96COP/Vanes

A record of Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic.

Information

Performance data for chiller model. This data corresponds to the following EnergyPlus model:
Chiller:Electric:ReformulatedEIR,
    ReformEIRChiller York YT 1758kW/5.96COP/Vanes,  !- Name
    1758300,                 !- Reference Capacity {W}
    5.96,                    !- Reference COP {W/W}
    5.56,                    !- Reference Leaving Chilled Water Temperature {C}
    32.23,                   !- Reference Leaving Condenser Water Temperature {C}
    0.06309,                 !- Reference Chilled Water Flow Rate {m3/s}
    0.06309,                 !- Reference Condenser Water Flow Rate {m3/s}
    ReformEIRChiller York YT 1758kW/5.96COP/Vanes CAPFT,  !- Cooling Capacity Function of Temperature Curve Name
    ReformEIRChiller York YT 1758kW/5.96COP/Vanes EIRFT,  !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
    ReformEIRChiller York YT 1758kW/5.96COP/Vanes EIRFPLR,  !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
    0.10,                    !- Minimum Part Load Ratio
    1.01,                    !- Maximum Part Load Ratio
    1.0,                     !- Optimum Part Load Ratio
    0.10,                    !- Minimum Unloading Ratio
    Chilled Water Side Inlet Node,  !- Chilled Water Inlet Node Name
    Chilled Water Side Outlet Node,  !- Chilled Water Outlet Node Name
    Condenser Side Inlet Node,  !- Condenser Inlet Node Name
    Condenser Side Outlet Node,  !- Condenser Outlet Node Name
    1.0,                     !- Compressor Motor Efficiency
    2.0,                     !- Leaving Chilled Water Lower Temperature Limit {C}
    ConstantFlow,            !- Chiller Flow Mode Type
    0.0;                     !- Design Heat Recovery Water Flow Rate {m3/s}

Attributes

NameValue
QEva_flow_nominal-1758300
COP_nominal5.96
PLRMin0.10
PLRMinUnl0.10
PLRMax1.01
mEva_flow_nominal1000*0.06309
mCon_flow_nominal1000*0.06309
TEvaLvg_nominal273.15 + 5.56
TConLvg_nominal273.15 + 32.23
TEvaLvgMin273.15 + 5.56
TEvaLvgMax273.15 + 10.00
TConLvgMin273.15 + 21.29
TConLvgMax273.15 + 33.53
capFunT{8.075668E-01, 5.287917E-02, -4.493793E-04, 7.036068E-03, -3.536822E-04, 3.731438E-04}
EIRFunT{2.593808E-01, -1.873181E-03, -4.808688E-04, 3.822020E-02, -3.813018E-04, -2.995903E-04}
EIRFunPLR{1.303414E-01, 1.618347E-02, -7.157278E-05, -1.337481E-01, 1.186910E+00, -1.240299E-02, 0.000000E+00, -2.328976E-01, 0.000000E+00, 0.000000E+00}
etaMotor1.0